Author:jiujiu Release time:2026-09-16 20:41:31 Number of views:59order
The cable stops advancing and won't move forward or backward. Pulling harder only increases tension without progress.
Duct obstruction (debris, collapsed conduit, displaced joints)
Insufficient lubrication
Grip snagging on a duct joint
Excessive cable weight in a long vertical section
Multiple cables binding inside an overfilled duct
Last resort: Pull the cable back out completely, inspect the duct with a camera, clear the obstruction, and restart with fresh lubricant.

Tension readings climb steadily during the pull, approaching or exceeding the cable's rated limit.
Insufficient or incorrect lubricant
Too many bends without pulleys
Duct fill ratio too high (cable too large for duct)
Rough or damaged duct interior
Pulling speed too fast
The rodder or cable encounters a hard stop at a specific point in the duct — often at the same location on every attempt.
Construction debris left in new ducts
Soil or rock intrusion through damaged joints
Rodent nesting or animal debris
Collapsed or crushed conduit sections
Misaligned duct joints
Visible cuts, abrasions, or crush marks on the cable jacket after pulling. Often discovered at termination or during testing.
Sharp edges at duct entries and pull boxes
Debris inside the duct
Grip applied incorrectly (too short mesh coverage)
Dragging cable over rough surfaces
Over-tension causing jacket thinning
The fiberglass duct rodder stops progressing inside the duct and buckles or loops back at the entry point when pushed.
Obstruction ahead of the rod tip
Rod diameter too small — flexing instead of pushing
Tight bend immediately after entry
Damaged rod tip catching on joints
Rod losing stiffness from age or damage
The cable develops twists, loops, or sharp kinks during payout or pulling, often near the reel.
No swivel between pulling line and cable
Reel payout issues (cable coming off reel incorrectly)
Improper reel stand setup
Pre-existing coil memory in the cable
The rodder, leader, or pulling rope snaps mid-pull — the cable is left stranded in the duct.
Exceeding the rodder/rope rated strength
Worn or damaged pulling equipment
Sharp edge cutting the pulling line
Shock loading (sudden tension spikes)
Knots or damaged sections in the pulling line
| Check | Action |
|---|---|
| Duct condition | Clean, inspect, and verify clear before pulling |
| Lubrication | Apply correct lubricant at entry, bends, and access points |
| Pulleys | Install at all bends, transitions, and every 20-30m on long runs |
| Grip & swivel | Correct size, proper installation, swivel in line |
| Equipment | Inspect rodder, reel stand, and winch; verify ratings |
| Tension monitoring | Set up tension meter; agree on maximum acceptable value |
| Team communication | Agree on stop signals before starting |